The selection of surge protector (SPD), the power supply system (according to the concept of lightning protection zone of 1EC62305-4 (EN62305-4), the establishment of advanced lightning strike and surge protection system for electrical equipment, is to protect complex electrical and electronic equipment An indispensable basic condition for trouble-free and damage-free operation. For the SPD requirements of lightning strike and surge protection systems in lightning protection zones specified in 1EC62305-4 (EN62305-4), in IEC60364-5-53/A2 (IEC64 /1168/CDV:2001) has relevant regulations.
Surge Protector (SPD) Selection
SPDs used as part of building fixtures are classified as "Class 1", "Class 2" and "Class III" SPDs according to EC61643-1 (EN61643-11). Depending on the installation site they choose, they are tested separately for different requirements and their loads.
Surge Protector (SPD) Selection - Rating
For the selection of surge protector (SPD), the discharge capacity of the first-level SPD is the highest. It is mainly used for the protection of LPZ0~LPZ1 and higher lightning protection zones in lightning strike and surge protection systems, as shown in the figure below. These protection devices must be able to discharge the lightning impulse current with a waveform of 10/350us multiple times and ensure that they will not be damaged. Level 1 SPDs are also known as lightning current protectors, and their main task is to prevent the intrusion of destructive partial lightning impulse currents into electrical equipment in the building.
Surge Protector (SPD) Selection - Primary Surge
The selection of surge protector (SPD), at the interface of LPZO to LPZ1 and higher lightning protection zones, or the interface of LPZ1 to LPZ2 and higher lightning protection zones, the discharge capacity is about tens of kiloamperes (8 /20μs waveform) class 2 surge protector.
Surge Protector (SPD) Selection - Secondary Surge
The selection of surge protector (SPD), the last link of the lightning strike and surge protection system of power supply equipment is the protection of terminal equipment (located in LPZ2~LPZ3 and higher lightning protection zones). The third-level protection (terminal protection) is mainly to prevent residual surges between lines in the power supply system (such as surges between L-N) and various operating overvoltages.