Lightning Protection Zones Concept
To ensure providing the ef fective lightning protection solution for power supply system and IT system, we should
know well the Lightning Protection Zones Concept from IEC 62305.
Protection measures such as LPS (Lightning Protection System), shielding wires, magnetic shields and SPD
determine LPZ (Lightning Protection Zones).
LPZ downstream of the protection measure are characterized by signif icant reduction of LEMP than that upstream
of the LPZ. With respect to the threat of lightning, the following LPZs are defi
ned (see the below fi
gures):
LPZ 0A zone where the threat is due to the direct lightning f lash and the full lightning electromagnetic f ield.
The internal systems may be subjected to full or partial lightning surge current;
LPZ 0B zone protected against direct lightning f lashes but where the threat is the full lightning electromagnetic
f ield. The internal systems may be subjected to partial lightning surge currents;
LPZ 1 zone where the surge current is limited by current sharing and by SPDs at the boundary. Spatial shielding
may attenuate the lightning electromagnetic f ield;
LPZ 2... n zone where the surge current may be further limited by current sharing and by additional SPDs at the
boundary. Additional spatial shielding may be used to further attenuate the lightning electromagnetic f ield.
As a general rule for protection, the object to be protected shall be in a LPZ whose electromagnetic characteristics
are compatible with the capability of the object to withstand stress causing the damage to be reduced (physical
damage, failure of electrical and electronic systems due to over-voltages).

The SPDs selected and their integration into the overall electrical system and IT system inside the structure shall
ensure that the partial lightning current will mainly be diverted into the earthing system at the interface LPZ 0A/
LPZ 1. Once the majority of the energy of the partial lightning current has been diverted via the f irst SPD, the
subsequent SPDs need to be designed only to cope with the remaining threat from the interface LPZ 0A to LPZ 1
plus the induction ef fects from the electromagnetic fi
eld withinLPZ 1 (especially if LPZ 1 has no electromagnetic
shield).
Lines entering from LPZ 0A (where direct f lashes are possible) carry partial lightning currents.
At the interface LPZ 0A to LPZ 1 therefore, SPDs tested with Iimp (Class I tested SPD) are needed to divert these
currents. Lines entering from LPZ 0B (where direct f lashes are excluded but the full electromagnetic fi
eld exists),
carry only induced surges. At the interface LPZ 0B to LPZ 1 the induced ef fects should be simulated by means of
either a surge current with a waveshape 8/20 μs (Class II tested SPD) or an adequate combination wave test (Class
III tested SPD) according to IEC 61643-1.