Axial-flow fans with four or six blades and diameters of 6–18 ft are typically employed in air-cooled heat exchangers, although larger and smaller fans are occasionally used as well. Plastic fan blades are used for air temperatures up to 175°F; metal (usually aluminum) blades are required for higher air temperatures.
Electric motors are most frequently used as fan drivers, but steam turbines are also used. Motor size is generally 50 hp (37 kW) or less. Speed reduction is usually accomplished using V-belts, high-torque-drive (HTD) belts, or reduction gear boxes. Hydraulic variable-speed drives may also be used. V-belt drives are limited to motor sizes of 30 hp (22 kW) or less, while HTD can be used with motor sizes up to 50 hp [6] and is the most widespread.
Variable-pitch fans are commonly used to provide process-side temperature control in air-cooled exchangers. The blade pitch is automatically adjusted to provide the required air flow to maintain the desired outlet temperature of the process fluid. This is accomplished using a temperature controller and a pneumatically operated blade adjustment mechanism. Reducing air flow also reduces power consumption when the ambient temperature is low. Similar results can be achieved using variable-speed drives.
The fans are situated in bays, which are self-contained sections of an air-cooled heat exchanger. A bay consists of one or more tube bundles, the fans and drive assemblies that supply air to the bundles, and the associated framework and support structures. Except in unusual circumstances, multiple tube bundles are placed side by side in the bay. Bays are usually designed for one to three fans, with two-fan bays being most common.
Fan bays can be preassembled and shipped to the plant site provided they are small enough to meet transportation requirements. Otherwise, they must be assembled in the field, which adds to the cost of the heat exchanger. An air-cooled heat exchanger consists of one or more fan bays, with multiple bays operating in parallel.