1.
Axial flow fans. For a given flow rate an axial flow fan is considerably more compact than the corresponding centrifugal fan, and fits very conveniently into a duct of circular cross-section. The fan static pressure per stage is limited, typically to a maximum of about 600 Pa at the design point, while the fan dynamic pressure is about 70% of the total pressure. Fan total efficiencies are in the range 65–75%. Axial flow fans mounted within a bifurcated duct, so that the motor is external to the gas flow, are a type commonly used in individual exhaust dilution systems. An axial flow fan is a good choice as a spot fan, or for mounting in a cell wall without ducting, but should not be used in highly contaminated air flows or diluted exhaust systems. Multistage units are available, but tend to be fairly expensive.
2.
Centrifugal fans, flat blades, backward inclined. This is probably the first choice in most cases where a reasonably high pressure is required, as the construction is cheap and efficiencies of up to 80% (static) and 83% (total) are attainable. A particular advantage is the immunity of the flat blade to dust collection. Maximum pressures are in the range 1–2 kPa.
3.
Centrifugal fans, backward curved. These fans are more expensive to build than the flat-bladed type. Maximum attainable efficiencies are 2–3% higher, but the fan must run faster for a given pressure and dust tends to accumulate on the concave faces of the blades.
4.
Centrifugal fans, aerofoil blades. These fans are expensive and sensitive to dust, but are capable of total efficiencies exceeding 90%. There is a possibility of discontinuities in the pressure curve due to stall at reduced flow. They should be considered in the larger sizes where the savings in power cost are significant.
5.
Centrifugal fans, forward curved blades. These fans are capable of a delivery rate up to 2.5 times as great as that from a backward inclined fan of the same size, but at the cost of lower efficiency, unlikely to exceed 70% total. The power curve rises steeply if flow exceeds the design value.