1. SPD general installation requirements
The surge protector adopts 35MM standard rail installation
For fixed SPDs, the following steps should be followed for general installation:
1) Determine the discharge current path
2) Mark the wires that cause additional voltage drops at the equipment terminals.
3) To avoid unnecessary induction loops, the PE conductor of each device should be marked,
4) Establish an equipotential connection between the device and the SPD.
5) To carry out the energy coordination of multi-level SPD
In order to limit the inductive coupling between the installed protected parts and the unprotected parts of the equipment, certain measurements are required. The mutual inductance can be reduced by the separation of the induction source and the sacrificial circuit, the selection of the loop angle and the limitation of the closed loop area.
When the current-carrying component wire is part of a closed loop, the loop and induced voltage are reduced due to the proximity of this wire to the circuit.
In general, it is better to separate the protected conductors from the unprotected conductors, and it should be separated from the grounding conductor. At the same time, in order to avoid transient orthogonal coupling between power cables and communication cables, necessary measurements should be made.
2. SPD grounding wire diameter selection
Data cable: It is required to be larger than 2.5mm2; when the length exceeds 0.5 meters, it is required to be larger than 4mm2. YD/T5098-1998.
Power cord: when the cross-sectional area of the phase line is S≤16mm2, the ground wire is S; 50054 Section 2.2.9
Main parameters of surge protector
1. Nominal voltage Un: The rated voltage of the protected system is consistent. In the information technology system, this parameter indicates the type of protector that should be selected, and it indicates the effective value of the AC or DC voltage.
2. Rated voltage Uc: the maximum voltage RMS that can be applied to the designated end of the protector for a long time without causing the characteristics of the protector to change and activate the protection element.
3. Rated discharge current Isn: The maximum impulse current peak value that the protector can withstand when a standard lightning wave with a waveform of 8/20μs is applied to the protector for 10 times.
4. The maximum discharge current Imax: the maximum impulse current peak value that the protector can withstand when a standard lightning wave with a waveform of 8/20μs is applied to the protector once.
5. Voltage protection level Up: the maximum value of the protector in the following tests: the flashover voltage with a slope of 1KV/μs; the residual voltage of the rated discharge current.
6. Response time tA: It mainly reflects the action sensitivity and breakdown time of the special protection element in the protector. The change in a certain period of time depends on the slope of du/dt or di/dt.
7. Data transmission rate Vs: indicates how many bits are transmitted in one second, unit: bps; it is the reference value for the correct selection of lightning protection devices in the data transmission system. The data transmission rate of lightning protection devices depends on the transmission mode of the system.
8. Insertion loss Ae: the ratio of the voltage before and after the protector is inserted at a given frequency.
9. Return loss Ar: It represents the proportion of the front wave reflected in the protection device (reflection point), which is a parameter to directly measure whether the protection device is compatible with the system impedance.
10. Maximum longitudinal discharge current: refers to the peak value of the maximum surge current that the protector can withstand when a standard lightning wave with a waveform of 8/20μs is applied to the ground for one time.
11. Maximum lateral discharge current: The maximum peak value of the surge current that the protector can withstand when a standard lightning wave with a waveform of 8/20μs is applied between the lines.
12. Online impedance: refers to the sum of the loop impedance and inductive reactance flowing through the protector under the nominal voltage Un. Often referred to as "system impedance".
13. Peak discharge current: There are two types: rated discharge current Isn and maximum discharge current Imax.
14. Leakage current: refers to the DC current flowing through the protector under the nominal voltage Un of 75 or 80