Surge Protector Graded Protection

The first-level lightning arrester can discharge the direct lightning current, or discharge the huge energy conducted when the power transmission line is directly struck by lightning. For places where direct lightning strikes may occur, CLASS-I lightning protection must be carried out. The second-level lightning arrester is a protective device for the residual voltage of the previous-level lightning arrester and the induced lightning strike in the area. When the front-level lightning strike energy absorption occurs, there is still a part of the equipment or the third-level lightning protection device. It is quite a huge amount of energy that will be transmitted over, which requires further absorption by the second-level lightning arrester. At the same time, the transmission line passing through the first-level lightning protection device will also induce the lightning strike electromagnetic pulse radiation LEMP. When the line is long enough, the energy of the induced lightning becomes large enough, and the second-level lightning protection device is required to further discharge the lightning strike energy. The third-level lightning arrester protects the LEMP and the residual lightning strike energy passing through the second-level lightning arrester.

first level of protection

The purpose is to prevent the surge voltage from being conducted directly from the LPZ0 area into the LPZ1 area, and to limit the surge voltage of tens of thousands to hundreds of thousands of volts to 2500-3000V.

The power supply lightning arrester installed on the low-voltage side of the household power transformer should be a three-phase voltage switching type power supply lightning protection device as the first-level protection, and its lightning current flow should not be lower than 60KA. This level of power surge arrester should be a large-capacity power surge arrester connected between each phase of the incoming line of the user's power supply system and the ground. It is generally required that this level of power surge arrester has a maximum impact capacity of more than 100KA per phase, and the required limit voltage is less than 2500V, which is called CLASS I power surge arrester. These electromagnetic arresters are designed to withstand the high currents of lightning and induced lightning strikes and to attract high-energy surges, diverting large surge currents to earth. They only provide limited voltage (when the surge current flows through the power surge arrester, the maximum voltage that appears on the line is called limiting voltage) as a medium level of protection, because the CLASS I level protector mainly absorbs large surge currents, only They cannot fully protect the sensitive electrical equipment inside the power supply system.

The first-level power lightning arrester can prevent lightning waves of 10/350μs and 100KA, reaching the highest protection standard specified by IEC. Its technical reference is: lightning current flow is greater than or equal to 100KA (10/350μs); residual voltage value is not greater than 2.5KV; response time is less than or equal to 100ns.

second level of protection

The purpose is to further limit the value of the residual surge voltage through the first-level lightning arrester to 1500-2000V, and implement equipotential bonding for LPZ1-LPZ2.

As the second-level protection, the power supply surge arrester output by the distribution cabinet line should be a voltage-limiting power supply surge arrester, and its lightning current capacity should not be lower than 20KA. It should be installed in the power supply for important or sensitive electrical equipment Circuit Distribution Office. These power surge arresters can better absorb the residual surge energy that has passed through the surge arrester at the user's power supply inlet, and have an excellent suppression effect on transient overvoltage. The maximum impact capacity required by the power lightning arrester used here is more than 45kA per phase, and the required limiting voltage should be less than 1200V, which is called CLASS II power lightning protection device. The general user power supply system can meet the requirements of the operation of the electrical equipment if the second-level protection is achieved.

The second-level power lightning arrester adopts the C-type protector for phase-to-neutral, phase-to-earth and middle-to-earth full-mode protection. The main technical parameters are: lightning current capacity greater than or equal to 40KA (8/20μs); residual voltage The peak value is not more than 1000V; the response time is not more than 25ns.

tertiary protection

The purpose is to ultimately protect the equipment by reducing the value of the residual surge voltage to less than 1000V, so that the energy of the surge will not damage the equipment.

When the power lightning arrester installed at the AC power inlet end of the electronic information equipment is used as the third-level protection, it should be a series-type voltage-limiting power supply lightning protection device, and its lightning current capacity should not be lower than 10KA.

The last line of defense can be a built-in power surge arrester in the power supply part of the electrical equipment to achieve the purpose of completely eliminating tiny transient overvoltages. The maximum impulse capacity required by the power lightning arrester used here is 20KA or lower per phase, and the required limiting voltage should be less than 1000V. It is necessary to have the third-level protection for some particularly important or sensitive electronic equipment, and it can also protect the electrical equipment from the transient overvoltage generated inside the system.

For the rectified power supply used in microwave communication equipment, mobile station communication equipment and radar equipment, it is advisable to select a DC power lightning arrester with an adapted working voltage as the final protection according to the protection requirements of its working voltage.

Level 4 and above

According to the withstand voltage level of the protected equipment, if two levels of lightning protection can limit the voltage to be lower than the withstand voltage level of the equipment, only two levels of protection are required. If the withstand voltage level of the equipment is low, four levels or even More levels of protection. The lightning current capacity of the fourth-level protection should not be lower than 5KA