Micro high pressure fan is a special type of fan. The micro high pressure fan can be seen as a fan that can be applied to occasions with relatively high wind pressure requirements. So how should such a micro high-pressure fan be loved for maintenance? This article will guide you through the maze.
maintain
① The fan and its system shall not operate with faults.
② The fan shall be kept and used by special personnel.
③ Regularly accumulate impurities such as dust and dirt inside the fan and prevent rust.
④ The maintenance of the fan must be carried out when it is shut down and powered off, and the main switch should be monitored by a dedicated person after power off.
⑤ Children, unrelated personnel, and people with limited mobility are prohibited from standing around during fan maintenance and commissioning.
⑥ During fan commissioning, no one is allowed to stand within 10 meters of the fan inlet and outlet direction.
⑦ Before and after fan maintenance, tools and other supplies should be counted to prevent being left inside the fan and pipeline.
⑧ In addition to replacing the lubricant after each repair, the lubricant should normally be replaced according to the actual situation.
Faults and causes
1. Severe vibration of fan
① The fan shaft is not concentric with the motor shaft, and the pulley groove is misaligned;
② Friction between the casing and the impeller or between the air inlet and the impeller;
③ Insufficient or unstable foundation stiffness;
④ Loose impeller rivets or impeller deformation;
⑤ Loose fitting of impeller shaft plate hole and shaft;
⑥ The connecting bolts of the casing, bearing block and bracket, bearing block and bearing cover are loose;
⑦ Poor installation of fan inlet and outlet pipes resulting in resonance;
⑧ The rotor is unbalanced due to dust accumulation, dirt, blade wear, impeller deformation, shaft bending, and other reasons on the blade.
2. Bearing temperature rise too high
① Severe vibration of the bearing box;
② The lubricant is of poor quality, deteriorated, or contains impurities such as dust, sand, dirt, or insufficient filling capacity;
③ The tightening force of the connecting bolts of the bearing box cover and seat is too large or too small;
④ The shaft and rolling bearing are installed askew, and the front and rear bearings are not concentric;
⑤ The rolling bearing is damaged or the shaft is bent.
3. Motor current too high or temperature rise too high
① The inlet and outlet pipe gates are not closed during driving;
② Low motor input voltage or single-phase power failure;
③ Affected by severe vibration of the bearing box;
④ The spindle speed exceeds the rated value;
⑤ The input gas contains viscous substances;
⑥ The ambient temperature is too low and the specific gravity is too large.
Scope of supply of complete sets of single machine products
1 fan, 1 supporting motor, 1 set of anchor bolts (4 sets of No4~6.3,4 sets, 8 sets of No7.1 and above), 1 set of coupling (No7.1~16).
To sum up, the maintenance of micro high-pressure fans is certain and very important. Only by properly maintaining the micro high-pressure fan can it be ensured that the micro high-pressure fan can work smoothly, thereby ensuring that industrial production can achieve higher efficiency and greater benefits.