How To Do A Good Job in Power Distribution Design Of High-voltage Suction And Supply Fan


As the god of safety in production and construction, the high pressure suction and supply fan has the necessity of installation. Its operation is directly related to the security of a region, so it should not be taken lightly during installation. If you want to install the high pressure suction fan and make it play a protective role, you need to do a good power distribution design for the high pressure suction fan. This article will give you directions.
The purpose of setting the high pressure suction and supply fan is to ensure personal safety and/or site safety, as well as to quickly handle accidents and restore the normal operation of the system as soon as possible. Its importance is beyond doubt. So, have we made the right electrical design for the power supply, operation mode and overload protection measures of the high-voltage suction and forced draft fan?
Relevant specification requirements of high-pressure suction and supply fan
Places that may suddenly release a large amount of harmful gases and explosive dangerous gases (or explosive dust) shall be provided with emergency ventilation (according to the process design requirements); The accident ventilation shall be equipped with corresponding detection (detection) alarm and control system according to the type of released substances; The manual control device for emergency ventilation shall be set at indoor and outdoor places convenient for operation; When the workplace is equipped with hazardous gas or explosive gas monitoring and alarm devices, the accident ventilation device shall be interlocked with the alarm device.
Accident ventilation is a necessary measure to ensure safe production and people's life safety; Accident ventilation does not include fire ventilation.
High-pressure suction and supply fan (i.e., emergency exhaust fan) is not only used for emergency ventilation (i.e., emergency exhaust fan), but also may be used for post-disaster smoke extraction or post-disaster ventilation after fire fighting, but it will never directly participate in fire fighting work as fire fighting fan.
Power supply of high pressure suction fan
The Shanghai landmark DGJ08-74-2004 Engineering Technical Specification for Gas Direct-fired Absorption Cooling and Heating Water Units clearly stipulates in Article 4.2.5: "The machine room where the unit is installed and the underground places where the gas pipeline passes through shall have independent mechanical air supply and exhaust system, and the emergency ventilation and air exchange rate shall not be less than 12 times/h. The emergency exhaust fan shall be explosion-proof and powered by the fire power supply."
The Shanghai landmark DGJ08-10-2004 Technical Code for Urban Gas and Natural Gas Pipeline Engineering clearly requires in Article 6.0.7 of "6 Gas for Public Buildings": "Gas boilers or gas direct-fired absorption cold and hot water units shall be installed in independent buildings with reliable performance alarms and emergency shut-off valves. Other technical requirements shall comply with the Shanghai Municipal Code for Engineering Construction "Technical Specification for Engineering of Gas Direct-fired Absorption Cooling and Heating Water Units" (DGJ08-74)
The National Technical Measures for the Design of Civil Building Engineering (2009 Edition), HVAC • Power, aims at the ventilation technical measures for boiler rooms, direct-fired lithium bromide refrigerator rooms and other equipment rooms: "The emergency exhaust fan shall be explosion-proof and powered by fire power."
It is recommended that the high pressure suction and supply fan be powered by fire power supply, or at least by power supply not lower than the highest load level of the construction project.
To sum up, the power distribution design of high pressure suction and forced draft fan is very particular, which needs to meet certain national standards and take into account production needs. The operating frequency of high-pressure suction and forced draft fan must meet certain conditions, otherwise it can not eliminate toxic substances. Therefore, the requirements for power distribution design are relatively high, and the feasibility must be ensured when formulating the design scheme.